Flameout Protection Of Steam Boiler

Jul 30, 2020

To prevent the occurrence of furnace explosion events, oil (gas) boilers must be equipped with flameout protection devices. The function is to monitor the combustion situation in the furnace (including ignition). When the ignition fails or the combustion is extinguished in the middle, it is generally re-ignited within 5 seconds, within 1 second Run, close the oil (gas) solenoid valve, turn on and send out an audible and visual alarm signal. At this time, the blower continues to run to purge the remaining combustible gas in the furnace. After 20-30 seconds of purging, the blower is automatically cut off And various auxiliary power supplies, the boiler stops running.) Consists of a flame monitor and a control device. The function of the flame monitor is to signal the presence or interruption of the flame from the control device.

The main ones used are photomultiplier tubes, photoresistors and photocells, all of which are ultraviolet or infrared, a type of photoelectric conversion element whose working principle converts the intensity of light radiation into corresponding strong and weak currents. And output in a linear state, sometimes the induced current is weak, and only through amplification can it have an effect on the controller.